Green indicates we consider our position best practice and not in dispute Grey items cover the December 2018 Amendments, Approved Documents and MHCLG's own FAQs and advice notes Green indicates that the item IS exempt from Regulation 7(2), in accordance with Regulation 7(3) Green indicates that B4 still applies, and refers to relevant parts
Yellow indicates our position has the potential to be subjective   Red indicates that the item is NOT exempt. Refer to Regulation 7(3) Red shows that B4 no longer applies

 

Warranty Position

Definition: Sealing tapes / membranes for sealing joints between sheathing boards/ membranes and adjoining structure.

Membranes and seals are exempt.

If the tapes / membranes being used for the sheathing boards can be demonstrated as being seals and / or membranes then only the AD B guidance needs to be accommodated.

Requirement: If a tape (max 150mm wide) that is not class B is proposed for these locations then an assessment confirming that compliance with B4-(1) has been achieved may be required.

Is the position indisputable? This may not be the view of all organisations.

December 2018 Amendment

Section 2 Reference: None.

Reference titles: None.


Approved Document

Reference title(s): 10.15(a).

References: Membranes used as part of the external wall construction above ground level should achieve a minimum of class B-s3, d0.


MHCLG FAQS / Advice Notes

Reference: Section 4.

Reference title(s): Approved Document B volume 2 paragraph 12.14 a. provides further guidance on membranes and provides that they should achieve at least Class B- s3, d0.

Exemptions

Is the item exempt from Regulation 7(2), in accordance with Regulation 7(3)?: Yes.

References: 7(3)(g) and 7(3)(h).

Statement: Membranes. Seals, gaskets, fixings, sealants and backer rods;

If exempt, are there any restrictions on the use of the system, component or material given in the guidance in ADB vol 2: Approved Document B clause 10.15(a) states "Membranes used as part of the external wall construction above ground level should achieve a minimum of class B-s3, d0."

Does B4 still apply?

Yes: Reference: B4-(1)

For guidance on using this resource, please click here.

Disclaimer: The information in this document is believed to be correct in light of information currently available and at the time of publication but is not guaranteed. Neither LABC Warranty nor its agents can accept responsibility in respect of the contents or any events arising from the use of the information contained within this site. The guidance provided does not replace the reader’s professional judgement and any construction project should comply with the relevant Building Regulations or applicable technical standards. For the most up to date LABC Warranty technical guidance please refer to your Risk Management Surveyor and the latest version of the LABC Warranty Technical Manual.